Most Recent Test Results for AMS


Most Recent Test Results for AMS

AMS received our most recent test results for our XT66 Casement Window, XT66 Single Door and XT66 Double Door Systems. Tests were carried out at ERC Test Centre in Leigh in the UK. All our systems tested exceeded the maximum requirements from the European standards. We are extreamly proud of our test results that will be of huge benefit to our customers.

 

Below are our test results:

 

XT66 Casement Window Test Results

 

Characteristic Classification standard Test or
calculation standard
Value Classification Result
Resistance to wind load EN 12210 EN 12211 2400Pa E2400C PASS
Water tightness EN 12208 EN 1027 900Pa AE900 PASS
Air Permeability EN 12207 EN 1026 600Pa 4 PASS
PAS 24: 2016         PASS

 

XT66 Single Door Test Results

 

Characteristic Classification standard Test or
calculation standard
Value Classification Result
Resistance to wind load EN 12210 EN 12211 2400Pa E2400C PASS
Water tightness EN 12208 EN 1027 750Pa AE750 PASS
Air Permeability EN 12207 EN 1026 600Pa 4 PASS
PAS 24: 2016         PASS

 

XT66 Double Door Test Results

 

Characteristic Classification standard Test or
calculation standard
Value Classification Result
Resistance to wind load EN 12210 EN 12211 2400Pa E2400C PASS
Water tightness EN 12208 EN 1027 750Pa AE750 PASS
Air Permeability EN 12207 EN 1026 600Pa 4 PASS
PAS 24: 2016         PASS

 

 

 

 